Internal register

A storage register held by the printer, with no other function. The PLC and software on the printer can both read and write it, which makes it a simple mailbox between the two.

PropertyValue
Data typesUINT16, INT16, UINT32, INT32, STRING, BLOCK
AccessR, or RW if the mapping is writable

There are two kinds:

  • Named internal registers can also be read and written through the Aurora API Modbus methods, for example by an extension. Their values are saved, and kept when the printer restarts.
  • Anonymous internal registers, with no name, are only reachable over Modbus. Their values are not saved, and are 0 after a restart.

A read-only named register is written only by software on the printer, so the PLC can use it to read results. A writable register can be written by both.

A BLOCK item holds raw 16-bit words, for data that the PLC and the software agree on, for example a packed structure.

Software on the printer can wait for the PLC to write a named register with waitModbusValue. Every write from the PLC or the API counts, even one that writes the same value.

Example​

In the example mapping list, the PLC writes requests to plc_request at 100, and an extension answers in aurora_reply at 101, which is read-only for the PLC:

StepWhoDoes
1PLCWrites 7 to register 100.
2ExtensionSees the write with waitModbusValue {"name": "plc_request", ...}, and handles request 7.
3ExtensionCalls setModbusValue {"name": "aurora_reply", "value": 7}.
4PLCReads 7 from register 101, and knows the request is done.

See Exchanging data with an extension for the full example.