Data types

All multi-byte values are big-endian, as required by Modbus.

TypeRegistersRange or content
UINT1610 to 65535
INT161−32768 to 32767, two's complement
UINT3220 to 4294967295, high word first
INT322−2147483648 to 2147483647, two's complement, high word first
STRINGlengthText, two bytes per register, see Strings
BLOCKlengthRaw 16-bit words with no interpretation

BLOCK is only used for internal registers and reserved ranges.

32-bit values​

32-bit values use big-endian word order: the register at the lower address holds the most significant 16 bits. PLC tools call this "high word first", "big-endian" or "ABCD".

For example, the value 123456 (0x0001E240) is sent as two registers:

RegisterValue
first (lower)0x0001
second (higher)0xE240

If a 32-bit value reads back with its halves swapped (123456 reads as 3795845121), the tool is configured for little-endian word order.

Saturation​

A value that does not fit the item's type is saturated to the nearest value the type can hold when read. It is never wrapped. For example, a counter at 70000 reads as 65535 through a UINT16 item, and a negative value reads as 0 through an unsigned item.

Use a 32-bit type for any value that can exceed 65535.

Strings​

A STRING item of length L occupies L registers and holds up to 2·L bytes of UTF-8 text. The bytes are packed two per register, the first byte in the high byte of the register:

"AB12" → 0x4142 0x3132
"ABC" → 0x4142 0x4300

When read, text shorter than the item is padded with NUL (0x00) bytes, and text longer than the item is truncated.

When written, trailing NUL bytes are removed before the text is used. A client may therefore either write the whole item, padded with NUL bytes, or write only the registers it needs, starting at the item's first register:

  • A function 16 write that starts at the item's first register may stop before the end of the item. The rest of the item is cleared.
  • A function 06 write to the item's first register writes one register, that is up to two bytes, and clears the rest of the item.

Written text must be valid UTF-8, otherwise the write returns exception 03. Plain ASCII is always valid UTF-8. Characters outside ASCII take two to four bytes each, so fewer of them fit in an item.

Example​

The lot number L0042, written to the 8-register item at address 2 in the example mapping list:

Register2345–9
BytesL 00 42 NULNUL
Value0x4C300x30340x32000x0000

Writing only registers 2–4 gives the same result.

Many PLCs store strings with a length byte or in little-endian byte order. Convert to the layout above before writing, and after reading.